Wednesday, April 15, 2009

SOLUTION3

Here at MAX-lab National Laboratory, Sweden we have for some years use Products from Klinkmann Automation with success. Our application is almost identical to yours. We use hardware such as ControlLogix,SLC500 and Siemens S7. As a alarm OPC server we use RSView32 and as OPC alarm client we use Klinkmanns GSM-Control. Our GSM-modem is a Siemens TC35 Currently we have some 50 alarms and send them to 5 mobilephones. Klinkmann ( http://www.klinkmann.com ) sell a kit for about 1510 EUR (2417 AUD) and it contains:GSM-Control software with HASP dongle keySiemens TC35IT modem, antenna, power supply and modem cable.
One thing I have notice is if you shut down RSView (for maintanence) you have to restart GSM-control (Connection with RSView OPC server is lost). Maybe there is a workaround for this described in the manual.
Best regardsLars-G JohanssonMAX-lab National laboratorySweden